EasyManuals Logo

gefran ADV200 Functions Description And Parameters List

gefran ADV200
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
ADV200 Functions description and parameters list 91
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.15 2244SpeedregIdissrc LINK 16/32 6000 0 16384 ERW F_S
Selection of the origin (source) of the signal for Enabling/disabling of the Integral part of the Speed regulator (Null=
enabled). The signal to be associated with this function can be selected from the “L_DIGSEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.16 2246SpeedregPfactor perc FLOAT 16/32 0 0 0 ER F_S
Monitoring of the Proportional part of the speed regulator output.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.17 2248SpeedregIfactor perc FLOAT 16/32 0 0 0 ER F_S
Monitoring of the Integral part of the speed regulator output.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.18 2240Inertia kgm
2
FLOAT SIZE 0.001 100.0 RWZS F_S
Setting of the inertia compensation coefcient. An increase in the dynamic response of the speed regulator to
a variation in the reference, can be modied by changing the current value during the acceleration/deceleration
phase, to counter the applied machine inertia.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.19 2242Bandwidth rad/s FLOAT SIZE 1.0 500.0 RWZS F_S
Setting of the bandwidth. Increasing the setting of this parameter increases the dynamic response and makes
the system more rigid.

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals