LED display Description Possible causes Corrective action
FirE
Fire mode
enabled
Fire mode enabled Fire mode enabled.
Check the environment and confirm the
fire status. If no fire, turn off the power and
power on again.
AdCEr
Voltage on
C/B error
The voltage on the control board
error
Errors of detecting voltages
Noises too much
Control board failure
Check the voltage on the control board.
EPErr
EEPROM
Save error
The data save in EEPROM is
wrong.
EEPROM circuit failure
Parameter check error after power on
Restore factory setting, then cut off the
power and power on again.
If warning again, replace control board.
bdErr
Control board
error
Firmware can’t meet Control
board.
Firmware can’t meet Control board.
Replace the control board (Please contact
Gefran Technical Assistance).
LOC
Parameter Lock
Parameter lock key code (pass-
word) already locked
• Parameter lock key code already enable
(13-07)
• Lifting the parameter lock key code, to enter
the correct parameter for 13-07
Err2
Set password failed
Parameter lock key code cannot
enable
• To enable the parameter lock key code (pass-
word) function, but the password is not correct
• Enter the correct parameter for 13-07 to
enable the parameter lock key
74 VDI100 • Start-up and Installation Manual