Troubleshooting
40 Installation Guidelines For 60 Hz EcoGen™ Generators
Generator Troubleshooting and System Diagnosis
To clear an active alarm, press the OFF button, ENTER button, then press AUTO. Contact an Independent Authorized
Service Dealer (IASD) if the alarm reoccurs.
Table 8-2. Generator Troubleshooting
Active Alarm LED Problem
Things to
Check
Solution
BATTERY
PROBLEM
YELLOW
Yellow LED illumi-
nated in any state.
Check the
screen for addi-
tional informa-
tion.
Contact Independent Authorized Servicing Dealer.
CHARGER
WARNING
YELLOW
Yellow LED illumi-
nated in any state.
Check the
screen for addi-
tional informa-
tion.
Contact Independent Authorized Servicing Dealer.
FUSE
PROBLEM
RED
Unit will not start
in AUTO with
remote two-wire
start set to the ON
(CLOSED)
position.
Check the
LEDs/Screen for
alarms.
Check ATO 7.5 Amp fuse. Replace with same type fuse if
bad. Contact Independent Authorized Servicing Dealer if
fuse is good.
HIGH
TEMPERATURE
RED
Unit shuts down
during operation.
Check the
LEDs/Screen for
alarms.
Check ventilation around the intake, exhaust and rear of
generator. Contact an Independent Authorized Servicing
Dealer if no obstruction is found.
INSPECT
BATTERY
YELLOW
Yellow LED illumi-
nated in any state.
Check the
screen for addi-
tional informa-
tion.
Inspect battery. Press ENTER to clear.
LOW BATTERY YELLOW
Yellow LED illumi-
nated in any state.
Check the
screen for addi-
tional informa-
tion.
Clear alarm. Using the control panel, check the battery by
navigating to the BATTERY MENU option from the MAIN
MENU. If battery condition displays GOOD, contact an
IASD. If control panel displays CHECK BATTERY, replace
the battery.
LOW OIL
PRESSURE
RED
Unit will not start
in AUTO with
remote two-wire
start set to the ON
(CLOSED)
position.
Check the
LEDs/Screen for
alarms.
Check oil level. Add oil per Owner’s Manual. Contact
Independent Authorized Servicing Dealer if oil level is
correct.
LOW VOLTS
REMOVE LOAD
RED
Unit will not start
in AUTO with
remote two-wire
start set to the ON
(CLOSED)
position.
Check the
LEDs/Screen for
alarms.
Clear alarm and remove loads from the generator. Set back
to AUTO and restart.
MISWIRE RED
Unit will not start
in AUTO with
remote two-wire
start set to the ON
(CLOSED)
position.
Check the
LEDs/Screen for
alarms.
Contact Independent Authorized Servicing Dealer.
NONE GREEN
Unit will not start
in AUTO with
remote two-wire
start set to the ON
(CLOSED)
position.
Check screen
for start delay
countdown.
If the start up delay is greater than expected, contact
Independent Authorized Servicing Dealer to adjust.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems EcoGen G0070340 and is the answer not in the manual?

Generac Power Systems EcoGen G0070340 Specifications

General IconGeneral
BrandGenerac Power Systems
ModelEcoGen G0070340
CategoryPortable Generator
LanguageEnglish

Related product manuals