COMMISSIONING
Getting The System Running
Ensure all connectors are firmly in place. Ensure that all connections are tight, with no stray strands of wire.
Ensure that the SIM CARD is securely fitted in the Panel and Repeaters. If a Junior Expansion Loop Card has
been added to the panel, please ensure that is securely fitted to the back of panel’s Main Board.
Power up the Panel.
Ensure that the Panel is in Installation Mode (SYSTEM ON LED flashing). If not, enter programming mode
and select function 8-4-1 Active/Installation Mode and put the panel into Installation Mode.
Press SYSTEM RESET.
Communications Check
Confirm that all Repeaters are showing identical information (LEDs and LCD) to that displayed by the
Panel.
Panel Check
Press and hold LAMP TEST on the Panel.
All the LEDs should light, the LCD backlight should turn on and all pixels on the LCD should be black. (See
page 28 Lamp Test)