- AUTOMATICALLY ACTIVATED OPERATION
PICTURE
1. Once the alarm is triggered, the car reaches either the
designated main evacuation floor or, if the fire is on the
main floor, a designated secondary evacuation floor.
2. When the applicable designated evacuation floor is
reached, the doors open and the lift remains “out of
service” until the fire alarm status is deactivated and the
automatic fire detection device is reset
3. Two evacuation plans can be established, a main one and a
secondary one.
4. While the lift is “out of service”, a luminous “no access”
signal on the designated evacuation floor push-button
panels warns users that the car cannot be entered and the
lift cannot be used.
5. The lift normally remains stationary on the evacuation
floor with the “doors open”, but it can be set to “doors
closed” if required by local regulations.
OUT OF SERVICE ON THE FLOOR
This is activated from the electrical cabinet when a fault occurs that requires the lift to be stopped.
• Once the alarm is triggered, the car reaches the main floor.
• When the main floor is reached, the doors open and the lift remains “out of service” until the fire alarm
status is deactivated and the electrical cabinet error is reset.