10 Technical Parameters
User Manual V1.1-2022-07-20
Technical Data GW73KLV-HT GW75K-HT GW80K-HT
Inrush Current (peak and duration)
(A)
120@1μs 120@1μs 120@1μs
Nominal Output Current (A) 191.6 114.0/108.3 121.6/115.5
Output Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion <3% <3% <3%
Maximum Output Overcurrent
Protection (A)
340 340 340
Eciency
Max. Eciency 98.4% 98.6% 98.6%
European Eciency 98.1% 98.3% 98.3%
Protection
PV String Current Monitoring Integrated
Internal Humidity Monitoring Integrated
PV Insulation Resistance Detection Integrated
Residual Current Monitoring Integrated
PV Reverse Polarity Protection Integrated
Anti-islanding Protection Integrated
AC Overcurrent Protection Integrated
AC Short Circuit Protection Integrated
AC Overvoltage Protection Integrated
DC Switch Integrated
DC Surge Protection Type II (Type I Optional)
AC Surge Protection Type II (Type I Optional)
AFCI Optional
Remote Shutdown Optional
PID Recovery Optional
PID Recovery
Operating Temperature Range (℃)
-30 ~ 60 (60 °C for outdoor unconditioned with solar
eects.)
Relative Humidity 0~100%
Max. Operating Altitude (m) 5000 (>4000 derating)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodwe HT Series and is the answer not in the manual?

Goodwe HT Series Specifications

General IconGeneral
Max DC Input Voltage1100V
MPPT Voltage Range200-1000V
Max AC Output Power3.6kW to 10kW
Number of MPPTs1 or 2
Max PV Input Voltage1100V
MPPT Range200-1000V
AC Output Frequency50/60Hz
CommunicationRS485, Ethernet
Operating Temperature Range-25°C to 60°C
Protection LevelIP65