10 Technical Parameters
Technical Data GW73KLV-HT GW75K-HT GW80K-HT
Input
Max.Input Power (kW) 112.5 112.5 120
Max.Input Voltage (V) 800 1100 1100
MPPT Operating Voltage Range (V) 180~650 180~1000 180~1000
MPPT Voltage Range at Nominal
Power (V)
250~650 500~850 500~850
Start-up Voltage (V) 200 200 200
Nominal Input Voltage (V) 370 600 600
Max. Input Current per MPPT (A) 30 30 30
Max. Short Circuit Current per MPPT
(A)
45 45 45
Max. Backfeed Current to The Array
(A)
0 0 0
Number of MPPT 12 10 10
Number of Strings per MPPT 2 2 2
Output
Nominal Output Power (kW) 73 75 80
Nominal Output Apparent Power
(kVA)
73 75 80
Max. AC Active Power (kW)
69@208V;
73@220V;
75@230V
75 88
Max. AC Apparent Power (kVA) 75 75 88
Nominal Power at 40℃ (kW) 73 75 80
Max Power at 40℃ (Including AC
Overload) (kW)
73 75 80
Nominal Output Voltage (V)
220, 3L/N/PE or
3L/PE
380/400, 3L/N/PE or 3L/PE
*1
Output Voltage Range (V) 187~242 320~440
Nominal AC Grid Frequency (Hz) 50/60 50/60 50/60
AC Grid Frequency Range (Hz) 47.5~51.5/57~61.8
Max. Output Current (A) 192.0 125.3 134.0
Max. Output Fault Current (peak and
duration) (A)
364@5μs 364@5μs 364@5μs

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodwe HT Series and is the answer not in the manual?

Goodwe HT Series Specifications

General IconGeneral
Max DC Input Voltage1100V
MPPT Voltage Range200-1000V
Max AC Output Power3.6kW to 10kW
Number of MPPTs1 or 2
Max PV Input Voltage1100V
MPPT Range200-1000V
AC Output Frequency50/60Hz
CommunicationRS485, Ethernet
Operating Temperature Range-25°C to 60°C
Protection LevelIP65

Related product manuals