DC INVERTER MULTI VRF PRODUCT
14
Model GMV(L)-R45P/Na-K GMV(L)-R50P/Na-K GMV(L)-R56P/Na-K
kW 4.5 5.0 5.6
Cooling Capacity
Btu 15355 17061 19108
kW 5.0 5.8 6.3
Heating Capacity
Btu 17060 19790 21496
m3/h 840 840 1400
Air Flow Rate
CFM 494 494 824
Sound Pressure Level (H/L) dB(A) 40/36 40/36 42/38
External Static Pressure Pa 40 40 100
Power Supply
220-240V~50Hz 220-240V~50Hz 220-240V~50Hz
Output kW 0.07 0.07 0.15
Fan Motor
Running Current A 0.69 0.69 1.32
mm
φ12.7 φ12.7 φ15.9
Gas Pipe
inch
1/2" 1/2" 5/8"
mm
φ6.35 φ6.35 φ9.52
Liquid Pipe
inch
1/4" 1/4" 3/8"
Connecting
Pipes
Connection Method Flare Connection Flare Connection Flare Connection
Drain Pipes
(External Dia. × Thickness)
mm
φ30×1.5 φ30×1.5 φ30×1.5
Unit Dimensions
(W×D×H)
mm
980×736×266 980×736×266 1112×756×300
Package Dimensions
(W×D×H)
mm
1068×766×320 1068×766×320 1245×785×360
Weight(Net/Gross)
kg 36/39 36/39 55/59
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.