5.4 SPH System Connection Mode
5.4.1
Conditions for DC Connection
WARNING
The solar modules connected to the inverter must conform to the Class A
requirements of the IEC 61730 standard.
Please use the same brand male and female PV connectors.
SPH single-phase inverter has 2 independent input : MPPT1& MPP
Notice that the connectors are in paired (male and female connectors).
CAUTION
If the inverter is not equipped with a DC switch but this is mandatory in the
country of installation, install an external DC switch.
The following limit values at the DC input of the inverter must not be exceeded:
Types Max current
MPPT1
Max current
MPPT2
SPH 3000-6000TL
BL-UP
13.5A 13.5A
Growatt
SPH3000-6000
13.5A 13.5A
5.4.2 Connecting the PV Array (DC input)
DANGER
Danger to life due to lethal voltages!
PV array supplies d.c voltage to inverter when exposed to light, before
connecting the PV array , Conver some light screens above PV arrays, ensure
that the DC switch and AC breaker are disconnect from the inverter. NEVER
connect or disconnect the DC connectors under load.
Make sure the maximum open circuit voltage(Voc) of each PV string is less
than the maximum input voltage of the inverter.
Check the design of the PV plant. The Max. open circuit voltage, which can
occur at solar panels temperature of -15, must not exceed the Max. input
voltage of the inverter.
WARNING
Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter. Only qualified personnel
can perform the wiring work.
Please dont connect PV array positive or negative pole to the ground, it
could cause serious damages to the inverter.
Check the connection cables of the PV modules for correct polarity and

Other manuals for Growatt SPH3600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPH3600 and is the answer not in the manual?

Growatt SPH3600 Specifications

General IconGeneral
ModelSPH3600
TypeHybrid Inverter
Rated Power3600 W
Max PV Input Voltage550 V
Number of MPPTs2
Max Input Current per MPPT11 A
Nominal DC Voltage360 V
Nominal AC Power3600 W
Max AC Current16 A
Nominal AC Voltage230 V
AC Voltage Range180-280V
Nominal Grid Frequency50/60 Hz
THDi<3%
Max Efficiency97.5%
DC SwitchYes
Protection DegreeIP65
Battery Voltage Range42 V - 59 V
Communication InterfacesRS485, WiFi
Max AC Power3600W
Euro Efficiency97.0%
Operating Temperature Range-25°C to +60°C
CoolingNatural Convection