Chart 6.11
Exportlimit is used for users to control the energy flowing to the grid. If this function is enabled, the feeding
power to grid will be equal or less than the setup value.
The purpose of the Fail Safe function is to ensure that should any part of the ELS fail, the Active Power
exported across the Connection Point will drop to the Agreed Export Capacity or less within the specified time.
Note: 1.Default value is 00.0%
2.Fail safe works only in meter mode
6. Under the default set, you can see the setup options below after pressing Enter:
Chart 6.12
Default set is “resume to default setting, please don't use it unless it's necessary.
6.5 Communication
6.5.1 Use of USB-A port
USB-A port is mainly for firmware update. Through USB connection, we can quickly update the software of
machine. You can see USB-A as below:

Other manuals for Growatt SPH3600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPH3600 and is the answer not in the manual?

Growatt SPH3600 Specifications

General IconGeneral
ModelSPH3600
TypeHybrid Inverter
Rated Power3600 W
Max PV Input Voltage550 V
Number of MPPTs2
Max Input Current per MPPT11 A
Nominal DC Voltage360 V
Nominal AC Power3600 W
Max AC Current16 A
Nominal AC Voltage230 V
AC Voltage Range180-280V
Nominal Grid Frequency50/60 Hz
THDi<3%
Max Efficiency97.5%
DC SwitchYes
Protection DegreeIP65
Battery Voltage Range42 V - 59 V
Communication InterfacesRS485, WiFi
Max AC Power3600W
Euro Efficiency97.0%
Operating Temperature Range-25°C to +60°C
CoolingNatural Convection