7 Start-up and shut down SPH system
7.1 Start-up the SPH system
Users can start-up SPH inverters through following steps:
1. Connect to PV
2. Connect to Grid
3. Connect to Battery
4. Turn the switch on in turn of Grid, battery and PV
5. When the LED turns green, the working information on LCD indicates the successful start-up of SPH
inverter
7.2 Disconnect the SPH system
1. Turn off all the circuit breaker and switch
2. Disconnect PV
3. Disconnect the inverter
4. Disconnect the battery
5. Pull up AC PLUG connection
6. Waiting until LED, LCD display have gone out, the SPH is shut down completely
8 Attention of the installation environment, maintenance and cleaning
Heat dissipation performance is very important when SPH inverter work under the environment of high
temperature, better heat dissipation can reduce the possibility of SPH inverter stops working. Growatt SPH
series inverter without fan so belongs to natural cooling, hot air from the top of the radiator, tie-in battery, use
environment for IP65, please pay attention to the temperature of the installation environment, to ensure that
the battery's safety and the normal work of the machine.
When use battery, please pay attention to the follow information:
Caution: Do not dispose of batteries in a fire. The batteries may explode.
Caution: Do not open or damage batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Caution: A battery can present a risk of electrical shock and high short-circuit current. The following
precautions should be observed when working on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source prior to connecting or disconnecting battery terminals.
Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such
shock can be reduced if such grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
If SPH inverter doesn't work for overheating or too cold, solve it according to the following methods
Confirm whether the radiator air duct installation is reasonable, choose the appropriate
position before installation.
If lead-acid batteries are connected, confirming the NTC battery is in a good installation

Other manuals for Growatt SPH3600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPH3600 and is the answer not in the manual?

Growatt SPH3600 Specifications

General IconGeneral
ModelSPH3600
TypeHybrid Inverter
Rated Power3600 W
Max PV Input Voltage550 V
Number of MPPTs2
Max Input Current per MPPT11 A
Nominal DC Voltage360 V
Nominal AC Power3600 W
Max AC Current16 A
Nominal AC Voltage230 V
AC Voltage Range180-280V
Nominal Grid Frequency50/60 Hz
THDi<3%
Max Efficiency97.5%
DC SwitchYes
Protection DegreeIP65
Battery Voltage Range42 V - 59 V
Communication InterfacesRS485, WiFi
Max AC Power3600W
Euro Efficiency97.0%
Operating Temperature Range-25°C to +60°C
CoolingNatural Convection