No AC Connection No Utility
Please confirm grid is lost or not.
Check the grid connection is good or not.
Check the switches on the cable are on or not.
Output High DCI
Output DC current too high.
Please refer to the local grid
standard for disconnection time
when the output DC current is
too high.
Restart inverter.
Please contact Growatt service center if restart can’t
solve the problem.
Bat Voltage High Battery Voltage higher than 60V
Check the voltage of battery is in the range of
specification or not.
Check the battery connection is right or not
If battery is really higher than 60V. Please disconnect
the connection of battery and check inverter.
Bat Voltage Low Battery Voltage Lower than 42 V
Check the real voltage of battery.
Check the wire of battery and inverter is good or
not.
BMS Warning:XXX BMS report warning
Check the warning information from lithium battery
user manual.
Please contact Growatt service center if restart can’t
solve the problem.
BMS error:XXX BMS report error
Check the warning information from lithium battery
user manual.
Please contact Growatt service center if restart can’t
solve the problem.
EPS Volt Low EPS output voltage low
Check the load of EPS. If overload occurred, reduce
load.
Restart inverter again.
Error Message
Error Message Description Suggestion
Error 411 Internal communication failed
Restart inverter.
Please contact Growatt service center if restart can’t
solve the problem.
Error 417 Sample fault
Restart inverter
Please contact Growatt service center if restart can’t
solve the problem
Error 418
DSP and COM firmware version
unmatch, system fault.
Read DSP and COM firmware version from LCD or
shinebus.
Check if the firmware is correct.
Error 303
Inverter L N reversed or ground
failed
Check the L line and N line is reversed or not.
Check the PE s connected well or not.

Other manuals for Growatt SPH3600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPH3600 and is the answer not in the manual?

Growatt SPH3600 Specifications

General IconGeneral
ModelSPH3600
TypeHybrid Inverter
Rated Power3600 W
Max PV Input Voltage550 V
Number of MPPTs2
Max Input Current per MPPT11 A
Nominal DC Voltage360 V
Nominal AC Power3600 W
Max AC Current16 A
Nominal AC Voltage230 V
AC Voltage Range180-280V
Nominal Grid Frequency50/60 Hz
THDi<3%
Max Efficiency97.5%
DC SwitchYes
Protection DegreeIP65
Battery Voltage Range42 V - 59 V
Communication InterfacesRS485, WiFi
Max AC Power3600W
Euro Efficiency97.0%
Operating Temperature Range-25°C to +60°C
CoolingNatural Convection