EasyManuals Logo

Grundfos CMBE User Manual

Grundfos CMBE
111 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
6. Startup
WARNING
Hot liquid
Death or serious personal injury
If the temperature is higher than 50 °C,
use gloves and glasses when venting
the pump to avoid risk of scalding.
WARNING
Biological hazard
Death or serious personal injury
Flush the pump with clean water
before first use.
Do not start the pump until it has been
filled with liquid.
Do not start the booster system until all
pumps have been properly primed.
After starting up the pump, check the
system for leakages.
6.1 Flushing the system
DANGER
Contaminated drinking water
Death or serious personal injury
Flush the system before starting it or
after a standstill period.
Drinking water systems
Hygiene
Grundfos pressure booster systems are functionally
tested by running water through the system. During
the test, Grundfos continuously surveys the quality of
the test water. Since it is not possible to completely
drain and dry the system after the test, the system
must be rinsed or flushed thoroughly before being
taken into use in a drinking water sector due to risk of
bacteria growth. This also applies if the system has
been shut down for a long period of time. Rinsing and
flushing must always be done in accordance with
local regulations.
Contaminated drinking water endangers health.
6.2
Supplement to quick guide
These instructions are a supplement to the quick
guide for CMBE and CMBE TWIN.
QR98388184
http://net.grundfos.com/qr/i/98388184
6.3 Priming and venting the product
1. Close the isolating valve on the outlet side.
2. Open the isolating valve on the inlet side.
3. Remove the priming plug.
4. Fill the pump with water until a steady stream of
liquid runs out of the filling hole.
5. Let all air out of the system.
6. Fit and tighten the priming plug.
15
English (GB)

Table of Contents

Other manuals for Grundfos CMBE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CMBE and is the answer not in the manual?

Grundfos CMBE Specifications

General IconGeneral
Flow RateUp to 6 m³/h
MaterialStainless Steel
Motor TypePermanent magnet motor
Liquid Temperature0°C to +60°C
Maximum Operating Pressure10 bar
Enclosure ClassIP55
Frequency50 / 60 Hz
Pump TypeCentrifugal pump
Power Supply1 x 200-240 V
ControlIntegrated Frequency Converter
Max Head60 m
Seal TypeMechanical seal
Motor Power0.3 - 1.5 kW

Related product manuals