Pos. Description
X: External input signal from 0 to 100 %
Y: Setpoint influence from 0 to 100 %
7.17 Predefined setpoints
Pump variant Predefined setpoints
NBE, NKE, NBSE, VLSE ●
NBE, NKE, NBSE Series
2000; VLSE with Delta ρ sensor
●
You can set and activate seven predefined setpoints by combining
the input signals with digital inputs 2, 3 and 4 as shown in the table
below. Set the digital inputs 2, 3 and 4 to Predefined setpoints if
all seven predefined setpoints are to be used. You can also set one
or two of the digital inputs to Predefined setpoints. However, this
limits the number of predefined setpoints available.
Digital inputs
Setpoint
2 3 4
0 0 0 Normal setpoint or Stop
1 0 0 Predefined setpoint 1
0 1 0 Predefined setpoint 2
1 1 0 Predefined setpoint 3
0 0 1 Predefined setpoint 4
1 0 1 Predefined setpoint 5
0 1 1 Predefined setpoint 6
1 1 1 Predefined setpoint 7
0: Open contact
1: Closed contact
Example
The figure shows how you can use the digital inputs to set seven
predefined setpoints. Digital input 2 is open, and digital inputs 3 and
4 are closed. If you compare with the table above, you can see that
Predefined setpoint 6 is activated.
0
1
2
3
4
5
6
7
DI 4
DI 2
DI 3
SP A
Stop
SP N
SP 1
SP 2
SP 4
SP 5
SP 6
SP 7
SP 3
TM070083
Pos.
Description
DI Digital input
SP Setpoint
SP
A
Actual setpoint
SP
N
Normal setpoint
Stop Stop
If all digital inputs are open, the motor stops or runs at the normal
setpoint. Set the desired action with Grundfos GO or with the HMI
300 or 301 operating panel.