7.25.12 Define Home display
The function is only available in the HMI 300 and 301 operating
panels.
Set the Home display to show up to four user-defined parameters.
7.25.13 Display settings
The function is only available in the HMI 300 or 301 operating
panels.
Use this function to adjust the display brightness. You can also set
whether or not the display is to switch off if no buttons have been
activated for a period of time.
7.25.14 Store settings (Store actual settings)
Use this function to store the current settings to enable the user to
go back to a previous set of settings.
7.25.15 Recall settings (Recall stored settings)
Grundfos GO
In this menu, you can recall stored settings from a number of
previously stored settings that the pump then uses.
Advanced operating panel
In this menu, you can recall the last stored settings that the pump
will then use.
7.25.16 Undo
The function is only available in Grundfos GO.
Use this function to undo all settings made with Grundfos GO in the
current communication session. Once you have recalled settings,
you cannot undo.
7.25.17
Pump name
The function is only available in Grundfos GO.
Use this function to give the motor a name. The selected name then
appears in Grundfos GO.
7.25.18
Connection code
Use the connection code to enable automatic connection between
Grundfos GO and the product. Thus, you do not need to press OK
or the Radio communication button each time.
You can also use the connection code to restrict remote access to
the product.
You can only set the connection code with Grundfos GO.
7.25.18.1
Setting a connection code in the product by using
Grundfos GO
1. Connect Grundfos GO to the product.
2. Go to Settings > General > Connection code.
3. Enter a connection code and press OK.
You can change the code in the Connection code menu at any
time. The old code is not required.
7.25.19
Run start-up guide
The function is only available in the HMI 300 and 301 operating
panels.
The startup guide automatically starts when you start the product
for the first time. You can always run the startup guide later. The
startup guide guides you through the general settings of the
product.
To run the startup guide, go to Settings > General settings > Run
start-up guide.
7.25.20
Alarm log
This function contains a list of logged alarms from the product. The
log shows the alarm code, name of the alarm, when the alarm
occurred and when the alarm was reset.
7.25.21
Warning log
This function contains a list of logged warnings from the product.
The log shows the warning code, name of the warning, when the
warning occurred and when the warning was reset.
7.25.22
Assist
This menu consists of a number of different assist functions.
Assist functions are small guides that take you through the steps
needed to set the product.
7.25.23 Assisted pump setup
This function guides you through the following:
Setting the motor
• Selection of control mode
• Configuration of feedback sensors
• Adjustment of the setpoint
• Controller settings
• Summary of settings.
With Grundfos GO, access the Assisted pump setup menu.
With the HMI 300 or 301 operating panel, access the Assisted
pump setup menu.
7.25.24 Setup, analog inputs
This function is only available in the HMI 300 and 301 operating
panels.
• Analog inputs, follow on-screen instructions.
• Pt100/1000 inputs, follow on-screen instructions.
7.25.25 Setting of date and time
The function is only available in the HMI 300 and 301 operating
panels.
The inputs and outputs available depend on the functional module
fitted in the motor.
Functional module
Setting of date and time
FM310 ●
FM311 ●
The function guides you through the following settings:
• Select date format
• Set date
• Select time format
• Set time.
7.25.26
Multipump function
The function Multi-pump function enables the control of two
motors connected in parallel without the use of external controllers.
The pumps or motors in a system communicate with each other via
the wireless GENIair connection or the wired GENI connection.
You can set a multipump system via the master motor, which is the
first selected motor.
If several pumps or motors in the system have sensors, they can all
function as the master and take over the master function if the other
fails. This provides additional redundancy in the multimotor system.
You can choose between the following multimotor functions:
Alternating operation
Alternating operation functions as a duty and standby operating
mode and is possible with two pumps or two motors of the same
size and type connected in parallel. The main purpose of the
function is to ensure an even amount of running hours and to
ensure that the other pump or motor starts if the duty pump or
motor stops due to an alarm.
You can choose between two alternating operating modes:
• Alternating operation, time
The change from one pump or motor to the other is based on
time.
• Alternating operation, energy
The change from one pump or motor to the other is based on
energy consumption.
61