Minimum contact current: 10 mA
Maximum contact current: 25 mA.
Input source rating: SELV
Bus input (Ethernet)
Protocols TC/IP GENI, GDP.
Cable type, Standard CAT5, CAT5e or CAT6.
Open-collector digital outputs (OC)
Current-sinking capability: 75 mADC, no current sourcing.
Load types: Resistive and/or inductive.
Low-state output voltage at 75 mADC: Maximum 1.2 VDC.
Low-state output voltage at 10 mADC: Maximum 0.6 VDC.
Overcurrent protection: Yes.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft (500 m).
Analog inputs (AI)
Voltage signal ranges:
0.5 - 3.5 VDC, AL AU
0-5 VDC, AU
0-10 VDC, AU.
Voltage signal:
Ri greater than 100 kΩ at 77 °F (25 °C).
Leak currents may occur at high operating temperatures. Keep the
source impedance low.
Current signal ranges:
0-20 mADC, AU
4-20 mADC, AL AU.
Current signal: Ri is equal to 292 Ω.
Current overload protection: Yes. Change to voltage signal.
Measurement tolerance: +/- 2 % of full scale.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft (500 m), excluding potentiometer.
Potentiometer connected to +5 V, GND, any AI: Use maximum 10
kΩ.
Maximum cable length: 328 ft (100 m).
Analog output (AO)
Current sourcing capability only.
Voltage signal:
Range: 0-10 VDC
Minimum load between AO and GND: 1 kΩ
Short-circuit protection: Yes.
Current signal:
Ranges: 0-20 and 4-20 mADC
Maximum load between AO and GND: 500 Ω
Open-circuit protection: Yes.
Tolerance: +/- 4 % of full scale.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft (500 m).
Pt100 or Pt1000 inputs (Pt)
Temperature range:
Minimum -58 °F (-50 °C) (80 Ω/803 Ω).
Maximum 399 °F (204 °C) (177 Ω/1773 Ω).
Measurement tolerance: +/- 2.7 °F (1.5 °C).
Measurement resolution: less than 0.54 °F (0.3 °C).
Automatic range detection (Pt100 or Pt1000): Yes.
Sensor fault alarm: Yes.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Use Pt100 for short wires.
Use Pt1000 for long wires.
LiqTec sensor inputs
Use a Grundfos LiqTec sensor only.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Grundfos Digital Sensor input and output (GDS)
Use Grundfos Digital Sensor only.
Power supplies, +5 V, +24 V
+5 V
Output voltage: 5 VDC -5 % to +5 %
Maximum current: 60 mADC, sourcing only
Overload protection: Yes.
+24 V
Output voltage: 24 VDC -5 % to +5 %
Maximum current: 200 mADC, sourcing only
Overload protection: Yes.
Digital outputs, relays
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
2
/ 28-12 AWG.
Maximum cable length: 1640 ft (500 m).
Bus input
Grundfos GENIbus protocol, RS-485.
Grundfos Modbus protocol, RS-485.
Screened 3-core cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft (500 m).
11.3 Other technical data
11.3.1 Ecodesign Directive
This product is out of scope of Directive 2009/125/EC and
Commission Regulation (EU) 2019/1781 due to Article 2 (3a), as
the variable speed drive (VSD) is integrated into a product and its
energy performance cannot be tested independently from the
product.
11.3.2
EMC (electromagnetic compatibility)
Standard used: EN 61800-3.
The table below shows the emission category of the motor.
C1 fulfils the requirements for residential areas.
Model J:
When connected to a public network, 15-HP
motors do not comply with the partial weighted harmonics
(PWH) requirements of EN 61000-3-12. If required by the
distribution network operator, compliance can be obtained
in the following way:
The impedance of the power cables between the motor
and the point of common coupling (PCC) must be
equivalent to the impedance of a 164 ft (50 m) cable.
Model K: This equipment complies with IEC 61000-3-12
provided that the short-circuit power S
SC
is greater than or
equal to the respective value described in the table below
at the interface point between the user's supply and the
public system. It is the responsibility of the installer or user
of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the
equipment is connected only to a supply with a short-
circuit power S
SC
greater than or equal to the respective
value described in the table below.