7.25.30 Factory settings
Function is enabled.
Function is disabled.
- Function is not available.
Settings NBE, NKE, NBSE, VLSE
NBE, NKE, NBSE Series 2000;
VLSE with Delta ρ sensor
Setpoint 67 % 58 %
Operating mode Normal Normal
Control mode Const. curve Prop. pressure
Date and time
Buttons on product
Controller (Controller settings)
T
i
0.5 0.5
K
p
0.5 0.5
Operating range
Min. 25 % 25 %
Max. 110 % 110 %
Ramps
Ramp-up 1 second 1 second
Ramp-down 3 seconds 3 seconds
Number (Pump number) 1 1
Radio communication
Analog input 1
12)
Analog input 2
Analog input 3
Grundfos Direct Sensor -
13)
Pt100/1000 input 1
Pt100/1000 input 2
Digital input 1 Ext. stop Ext. stop
Digital input 2
Digital input 3
Digital input/output 4
Predefined setpoints
Analog output
External setpoint funct.
Signal relay 1 Alarm Alarm
Signal relay 2 Ready Ready
Limit 1 exceeded
Limit 2 exceeded
Limit 3 exceeded
Limit 4 exceeded
Standstill heating
Motor bearing monitoring
12)
VLSE with Delta ρ sensor has the sensor connected to an analog input.
13)
Not VLSE with Delta ρ sensor.