5.5 Flushing
Fig. 14 Flushing process
5.6 Dosing control
The dosing control signal given to the dosing pump depends on
the type of pump:
A digital dosing pump needs a current signal 0(4)-20mA.
A mechanical dosing pump needs the voltage (power-on/
power-off) from the dosing control.
5.6.1 Control mode
The selected control mode depends on the application.
Proportional control
The proportional control mode is particularly suitable for drinking
water applications.
The dosing pump doses in proportion to the flow rate of the water
meter:
A water meter measures the flow rate in the main water line,
and continuously sends the measured values to the control.
The proportional control calculates the required ClO
2
dosing
volume in proportion to the water flow rate in the main line.
The proportional control sends an actuating variable to the
dosing pump.
The dosing pump doses the required quantity of ClO
2
solution
from the internal batch tank into the main water line.
An optional measuring cell monitors the ClO
2
concentration in
the main line.
Note
The system has to be flushed with water to remove
any traces of chemicals in the suction hoses, pumps
and reaction tank in the following situations:
Prior to decommissioning
prior to maintenance and repair.
TM06 0642 0914
Floater in reaction tank reaches
K1, HCl pump starts for 1:30 min
Time elapsed, solenoid valve
opens
flushing is running
Time elapsed, NaClO
2
pump starts
for 1:30 min
please wait!
NaClO2 pump
flushing is running
Floater in reaction tank drops to K1
put suct. lance into water [OK]
open drain cock [OK]
Waiting until the internal batch tank
is empty
close drain cock [OK]
Two cycles
done?
Solenoid valve opens
Content of reaction tank flows into
the internal batch tank.
Float in the internal batch tank
rises above K5, solenoid valve
closes
flushing is finished [Esc]
HCl pump
flushing
flushing
flushing
flushing
flushing
flushing
flushing
flushing
flushing
yes
no
control mode measurement water meter
proportional -
combined ●●
setpoint -