English (GB)
63
12.4 Packaging for transport
1. After the system frame has dried, place it in its original
packaging, add the suction lances and insulating material.
2. Pack the dry hoses in a box.
3. Pack the cables in a box.
4. Place the fixing screws in a bag and store in the box with the
cables.
5. For OCD-162-60: Attach the transport protection of the
NaClO
2
and HCl dosing pumps, see section 6.1 Transport.
6. If applicable, place the measuring cell and the accessories in
the original packaging, add insulating material and seal ready
for transport.
7. If applicable, place the bypass mixing module or the
measuring module and the installation accessories, cables
and hoses in the original packaging, add insulating material
and seal ready for transport.
8. Add the installation and operating instructions, and seal the
box ready for storage or transport. Include the delivery note.
12.5 Storage
The storage conditions (temperature, humidity, room conditions,
etc.) must correspond to the conditions at the installation site, see
sections 6.3 Mounting and 15. Overview spare parts,
maintenance kits and accessories.
12.6 Recommissioning
13. Disposal
The system must be flushed before dismantling in order to
remove the chemicals from the reaction tank, the internal batch
tank, the hoses and the pumps. The dosing line must be placed
outdoors to let residual ClO
2
escape.
Warning
For transportation, the OCD-162-030 and OCD-162-
060 systems have to be fastened on a pallet with
suitable screws.
Warning
When the system is dismantled, the screw
connection between the gas hose and the volume
compensation bag is disconnected to allow residual
gas to escape.
Remember to reconnect the gas hose when
reinstalling the system.
When the system is dismantled, the used activated
carbon filter or the adsorbent is removed and
disposed of.
Remember to fit a new activated carbon filter when
reinstalling the system.
The system and its associated parts must be
disposed of in an environmentally sound way. Use
appropriate waste collection services. If this is not
possible, contact the nearest Grundfos company or
service workshop.
The system may only be dismantled by authorised
service staff.
The operating company is responsible for ensuring
an environmentally friendly disposal.