57
B. Standard remote controller (with time-meter)
Pressing check button can confirm inspection code. Refer to item 2 for reading method of inspection
code:
(1) Check display operation
Press it for 0.5 second to display inspection
code
Press it for 3 seconds to reset the indoor unit
(when the indoor unit is in the state of stopping
running due to its abnormality)
Press it for 10 seconds to clear inspection
information in addition to resetting the indoor
unit.
When using it, press the button in the hole,
the power of remote controller will be reset
(clear all information)
Indoor unit group with cool mode being set due to prior to heat control
When the capability of indoor unit group is overloaded
Selection of indoor unit group whose running mode is opposite to the running mode
(cold/heat) and switch setting content of outdoor unit
When the phase sequence of power wiring of outdoor unit is wrong
LCD displays the reason of "standby"
Check button
Reset button
MODE
®
C
F
FAN
FAN ONLY
COOL
DRY
HEAT
AUTO
AUTO
HIGH
MED
LOW
FIX
CENTRAL
OPERATION
STANBY
PRENEAT
DEFROST
MODE
TEMP
LOVER
UNIT
CHECK
DEMAND MANUAL
TIMER CONT. OFF ON ADDRESS
AFTBR H M
REMOTE CONTROLLER
FAN LOU
TEMP
TIMER
CHECK FILTER
FILTER
ON/OFF