69
Installation
Before starting
Operation
Screen block
diagram
Function setting Program System setting Specifications
1. Operation after detection
- Error stop : DI error shows DI error screen and stops operation.
- Time stop : DI error shows DI error screen and stops operation after the setting time is elapsed.
- Error operation : DI error shows DI error screen and continues operation.
- Operation : DI error doesn't show DI error screen and continues operation.
- Setting time : For Time stop, it stops operation after the setting time is elapsed.
2. Detection delay : Delay after DI occurrence may be set by DI.
1. Enter a DI error name (using Korean, English, numeric, and symbol characters).
2. Entered DI error name is shown on DI error screen for the error.
3. A DI error name may include up to 24 characters (12 ones in Korean).
▶ Configuration setting
▶ DI name
Parameter Setting range Default
Operation after detection
Error stop, Time stop, Error operation, and Operation
Error stop
Setting time 0 - 9999 S 0 S
Operation channel Ch.1, Ch.2 and All All
Detection delay 0 - 9999 min 59 sec 0 S
Parameter Default Setting range
DI error name DI_ERRORnn Korean, English, numeric, and symbol characters
Fig. 115) DI configuration setting
Fig. 116) DI name Fig. 117) Enter a DI name