Admittance Smart Switch Series
Manual
Rev 1.2, June 2008
37
SPECIFICATIONS
Operating Voltage
• 7 - 30Vdc (residual ripple no greater than
100mV)
• 80 - 260Vac 50/60Hz
Power Consumption
• <0.8W @ 24Vdc
• <5VA @ 240Vac
• <3VA @ 115Vac
Communications
• GosHawk, Modbus
• Remote version also with HART,
Probus DP and DeviceNet (options)
• Multidrop mode can address 1-250 units
over 4 wires
Relay Output: (1) SMART (2) Remote
• Form ‘C’ (SPDT) contacts, rated 5A at
240Vac resistive
• Remote failsafe test facility for one relay.
Measurement Range
• 0.2pF - 100nF
Resolution
• 0.01 pF
Electronic Accuracy
• 0.05 pF
Stability
• 0.01% / °C
Operating Temperature
Remote electronics -40°C (-4F) to 80°C (176°F)
Smart Probe -4C (-40°F) to 450°C 842°F)*
Remote Probe -4C (-40°F) to 450°C (842°F)*
Probe/Amplier Separation
• up to 500m (1640ft) using specied exten-
sion cable
Cable type between Amplier and Probe
• 4 conductor shielded twisted pair instrument
cable.
Conductor size dependent on cable length.
BELDEN 3084A, DEKORON or equivalent.
Max: BELDEN 3084A = 500m (1640 ft)
Max: DEKORON IED183AA002 = 350m
(1150 ft)
Maximum Operating Pressure
• 2 BAR
Display (Remote version only)
• 2 line x 12 character alphanumeric LCD
• Backlight standard
Memory - Remote
• Non-Volatile (No backup battery required)
• >10 years data retention
Enclosure Sealing
• Smart Probe IP67
• Remote Electronics IP65 (Nema 4x)
• Remote Probe IP67
Cable Entries
BSP process mounting
• 2 x M20 glands
NPT process mounting
• 2 x 3/4” NPTF threaded adaptors
Remote
3 x 20mm (0.8), 1 x 16mm (0.6) knock outs
Mounting
• 3/4” NPT or BSP Thread
• 1” NPT or BSP Thread
• 1.5” NPT or BSP Thread
• 50mm (2”) Flange (ANSI, DIN or JIS
patterns available)
Remote Test Input
Press to test
(used to check for malfunction of
unit from remote position, PLC, SCADA etc)
*correct temperature range probe must be specied when ordering
Patents Pending

Other manuals for Hawk Gladiator

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hawk Gladiator and is the answer not in the manual?

Hawk Gladiator Specifications

Power IconPower
operating voltage12-30VDC, 90-260VAC, 36-60VDC
power consumption<0.8W @ 24VDC, <5VA @ 240Vac, <3VA @ 115Vac
Operating Environment IconOperating Environment
maximum operating pressure2 BAR
operating temperature for remote electronics-40°C (-40°F) to 80°C (176°F)
operating temperature for remote sensors-20°C (-4°F) to 80°C (176°F)
enclosure sealing for remote electronicsIP67 (NEMA 4x)
enclosure sealing for remote sensorsIP68
Weight and Dimensions IconWeight and Dimensions
transducer to amplifier separationUp to 500m (1640ft)
typical weight for 15kHz transducer8 kg
typical weight for remote amplifier1 kg

Related product manuals