3 Product Description F2 DO 16 01
Page 12 of 40 HI 800 159 E Rev. 2.00
WARNING
For connecting a load to a 1-pole switching output, use the corresponding L- ground of
the respective channel group (2-pole connection) to ensure that the internal protective
circuit can function.
Inductive loads may be connected with no free-wheeling diode on the actuator. However, HIMA
strongly recommends connecting a protective diode directly to the actuator.
If communication is lost, the output is set to the initial value configured. This effect must be
taken into account for the behavior of the connected output.
If an overload occurs, one or all digital outputs are switched off. If the overload is removed, the
outputs are switched on again automatically, see Table 12.
3.1.1.1 Reaction in the Event of a Fault
If the device detects a faulty signal on a digital output, the affected module output is set to the
safe (de-energized) state using the safety switches.
If a device fault occurs, all digital outputs are switched off.
In both cases, the devices activates the FAULT LED.
The error code allows the user to configure additional fault reactions in the user program.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HIMA HIMatrix F2 DO 16 01 and is the answer not in the manual?

HIMA HIMatrix F2 DO 16 01 Specifications

General IconGeneral
BrandHIMA
ModelHIMatrix F2 DO 16 01
CategoryController
LanguageEnglish

Related product manuals