3 Product Description F2 DO 16 01
Page 20 of 40 HI 800 159 E Rev. 2.00
3.5 Product Data
General
Response time 20 ms
Ethernet interfaces 2 x RJ-45, 10BASE-T/100BASE-Tx with integrated switch
Operating voltage 24 VDC, -15...+20 %, r
PP
15 %,
from a power supply unit with safe insulation
in accordance with IEC 61131-2
Current input
max. 9 A per group
Idle: approx. 0.2 A per group at 24 V
Fuse (external) 10 A time-lag (T)
Back-up battery None
Operating temperature 0...+60 °C
Storage temperature -40...+85 °C
Type of protection IP20
Max. dimensions
(without plug)
Width: 207 mm (with housing screws)
Height: 114 mm (with fixing bolt)
Depth: 66 mm (with earthing screw)
Weight approx. 0.9 kg
Table 11: Product Data
Digital outputs
Number of outputs 16 (non-galvanically separated)
Output voltage
L+ minus 2 V
Output current max. 2 A at < 40 °C
max. 1 A at 40…60 °C
Current per group
Total permissible current
max. 8 A
max. 16 A
Minimum load 2 mA for each channel
Lamp load
max. 10 W (with output 1 A)
max. 25 W (with output 2 A)
Inductive load max. 500 mH
Internal voltage drop max. 2 V at 2 A
Leakage current (with low
level)
max. 1 mA at 2 V
Behavior upon overload
The affected output is switched off and cyclically switched on
again
Table 12: Specifications for the Digital Outputs