Installation Octopus II
Release
06
10/2018
35
To protect the exposed uninstalled contacts of the components from dirt,
connect the individual system components in a dry and clean working area.
Note: Exclusively for device variants featuring temperature range
characteristic value T:
Mount the device on a 1.62 sq ft (0.15 m²) large, 0.09 in (2 mm) thick metal
plate to which you do not connect any other heat source. Otherwise the
maximum ambient temperature is reduced by 5 K.
See “General technical data” on page 49.
Prepare the drill holes at the installation point.
Mount the device on a level surface with 4 M5 screws.
To preserve the suitability of your device for IP65/67, proceed as follows:
Remove the provided transport protection caps and the transport
protection screws from the device.
Seal unused sockets and plugs with your desired type of protection
screws which you can order separately.
2.2.2 Grounding the device
Grounding the device is by means of a separate ground connection on the
device.
The overall shield of a connected shielded twisted pair cable is connected to
the ground connection on the metal housing as a conductor.
The device variants have a connection for protective grounding.
Note: Use toothed washers to ensure good electrical conductivity at the
connection.
Ground the device via the provided M4 screw.
M4x8