7 Test Run
180
SMGB0064 rev.0 - 08/2011
7.4 Test run procedure from the outdoor unit side
The test run procedure from the outdoor unit side is shown below.
You can set this DIP switch while the power source is ON.
Setting of dip switch
DSW1
1 Cooling: Pin 1 ON
2 Heating: Pin 1, 2 ON
3 Cooling intermediate season: Pin 1, 3 ON
4 Heating intermediate season: Pin 1, 2, 3 ON
5 Manual compressor OFF: Pin 4 ONe
D A N G E R
• Do not touch any other electrical components while you are setting the switches on the PCB.
• Do not attach or detach the service access panel when the power source for the outdoor unit is ON and the
outdoor unit is operating.
• Set all the DIP switches of DSW1 to OFF after completing the test run.
Dip switch seting Operation Remarks
Test run
1. Setting operation mode
• The indoor unit automatically
starts to operate when the
test run of the outdoor unit
is set.
• You can perform the ON/OFF
operation from the remote
control switch or the DSW1
of the outdoor unit.
• Continuous operation during
2 hours is performed without
the Thermo-OFF condition.
• Make sure that the indoor
units start to operate in
accord with the test run of
the outdoor unit.
• If you start the test run from
the outdoor unit and you stop
the test run from the remote
control switch, the test run
function of the remote control
switch is cancelled. Howe-
ver, the test run function
of the outdoor unit is not
cancelled.
• If the more than one indoor
unit is connected with one
remote control switch, all the
units start the test run at the
same time. Therefore, turn
OFF the power source so
that the indoor units do not
perform the test run. If this is
the case, the TEST RUN in-
dication of the remote control
switch may icker. This is not
abnormal.
• The setting of DSW1 is not
required for the test run from
the remote control switch.
(a) Cooling:
Set DSW1-1 ON
(b) Heating
SET DSW1-1 and 2 ON
(c) Cooling intermediate
season:
Set DSW1-1 and 3 ON
(d) Heating intermediate
season:
Set DSW1-1, 2 and 3 ON
Manual OFF of com-
pressor
2. Forced stoppage of compressor: • When DSW1-4 is ON during
the compressor operation,
the compressor stops
operating immediately and
the indoor unit is under the
Thermo-OFF condition.
• When DSW1-4 is OFF, the
compressor starts to operate
after the cancellation of the
3-minute guard.
• Do not turn ON and OFF the
compressor frequently
Set DSW1-1 ON