12  Maintenace notes
470
SMGB0064 rev.0 - 08/2011
12.9  Service and maintenance record
No. Check item Action Judgement
1 Is the service area sufcient? — Yes No
2 Is there a short circuit of the discharged air? — Yes No
3 Any heat inuence? — Yes No
4 Is the ground wire connected? — Yes No
5 Refrigerant piping. — Good Not Good
6 Fixing the units. — Good Not Good
7
Is there any damage on the outer surface or 
the internal surface?
— Yes No
8 Checking the screw and the bolts. Tighten if loosened. Tightened Not Tightened
9 Tightening the terminal screws.
Tighten all the terminal screws with a Phillips 
screwdriver.
Tightened Not Tightened
10 Are the compressor terminals tightly xed? Push all the terminals. Pushed Not Pushed
11 Insulation resistance.
Measure the insulation resistance with an insula-
tion resistance meter.
Comp. and fan.
motor: greater than 3MΩ.
Others: greater than 3MΩ.
Good Not Good
12 Does the drain water ow smoothly? Check the smooth ow by pouring some water. Good Not Good
13 Check for a leakage in the compressor. Check for any leakage. Good Not Good
14
Check for a leakage in the outdoor heat ex-
changer.
ditto Good Not Good
15
Check for a leakage in the indoor heat exchan-
ger.
ditto Good Not Good
16 Check for a leakage in the 4-way valve. ditto Good Not Good
17 Check for a leakage in the check valve. ditto Good No Good
18 Check for a leakage in the accumulator. ditto Good Not Good
19 Check for a leakage in the strainer. ditto Good Not Good
20
Check for a leakage in the electronic expansion 
valve
ditto Good Not Good
21 Check for a leakage in the piping. ditto Good Not Good
22 Check the direction of the fans. By viewing the airow volume. Good Not Good
23 Voltage among each phase. Higher than AC220V. Good Not Good
24 Vibration and sound.
Check the fan the compressor the piping and 
others.
Good Not Good
25 Activation of each operation mode.
Check the activation of the COOL switch the 
HEAT switch the STOP switch and the TEMP 
switch.
Good Not Good
26 High-pressure cut-out switch. Check the actual activation value. Good Not Good
27
Check the activation of the drain-up mecha-
nism.
Check the activation during the cooling process. Good Not Good
28 Air inlet temperature of the indoor unit DB/WB. — (°C)DB (°C)WB
29
Air outlet temperature of the indoor unit DB/
WB.
— (°C)DB (°C)WB
30
Air inlet temperature of the outdoor unit DB/
WB.
— (°C)DB (°C)WB
31
Air outlet temperature of the outdoor unit DB/
WB.
— (°C)DB (°C)WB
32 High-pressure switch. — kg/cm
2
G
33 Low-pressure switch. — kg/cm
2
G
34 Operating voltage. — V
35 Operating current. — A
36
Instructions to the client for cleaning the air 
lter.
— Done Not yet