11 Electrical checks of
main parts
458
SMGB0064 rev.0 - 08/2011
11.7 Reactor (DCL)
11.7.1 Reactor (DCL) for 3N~
This part is used for changing the alternative current to the direct current for the inverter.
RAS-(4-6)HRNM2E (400V/50Hz) / RAS-(4-6)HRNS2E (400V/50Hz) /
RAS-(8-12)HRNM (380-415V/50Hz) / RAS-(8/10)HRNSE (400V/50Hz)
Items Specications
Character 1.0 mH+10 (at 1 kHz)
Rated current 30 A
Direct resistance 22.8 mΩ+20 (at 20 °C)
Permissible temperature range -20 ºC to 60 ºC
11.7.2 Reactor (DCL) for 1~
This part is used for changing the alternative current to the direct current for the inverter.
RAS-(4-6)HVRNM2E (230V/50Hz) / RAS-(4-6)HVRNS2E (230V/50Hz)
Items Specications
Character 0.59 mH±15 (at 1 kHz)
Rated current 30 A
DC Resistance 26 mΩ (at 20 °C)
Permissible temperature range -20ºC to 60ºC