EasyManua.ls Logo

Hitachi RAS-(4-6)HVRNS2E - Refrigerant Charge Quantity for es Series

Hitachi RAS-(4-6)HVRNS2E
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Piping work and
refrigerant charge
58
SMGB0064 rev.0 - 08/2011
Refrigerant charge quantity for ES series
Outdoor units has been charged with refrigerant for ℓ(m) of actual piping length. An additional refrigerant charged is re-
quired in systems with actual piping length longer than ℓ(m).
Determine an additional refrigerant quantity according to the following procedure, and charge it into the system.
Record the additional refrigerant quantity to facilitate service activities thereafter.
C A U T I O N
- When charging refrigerant accurately measure refrigerant to be charged.
- Overcharging or undercharging of refrigerant can cause compressor trouble.
- In case of actual piping length less than 5 m, consult your distributor.
Outdoor unit Factory Refrigerant charge (Wo Kg) is the next:
O/U MODEL Wo (Kg) Chargeless Length ℓ(m) Additional Charge Factor (P)
RAS-2HVRN2 1.6 30 0.03
RAS-2.5HVRN2 1.6 30 0.03
RAS-3HVRNS2 1.9 20 0.03
RAS-4H(V)RNS2E 2.8 20 0.04
RAS-5H(V)RNS2E 2.9 30 0.06
RAS-6H(V)RNS2E 2.9 30 0.06
RAS-8HRNSE 6.0 30 0.065
RAS-10HRNSE 6.2 30 0.12
1 Refrigerant shall be added if L is longer than the chargeless length shown in the table above.
Calculate the additional amount as follows:
A. 30 m.
B. 8 m.
C. 8 m.
Chargeless Length : for 4HVRNS2E is 30 m according to
the table before.
Additional Correction Value P : for 4HVRNS2E, “0.04” ac-
cording to the table above.
Additional Charge amount W will be:
W= (L-ℓ) x P
Example: W= (36-20) x 0.04 = 0.64 (kg)
2 Charge the amount W calculated by point 1.
3 Setting of pipe length DSW.
DSW2 setting will be required only when the refrigerant pipe
length is shorter than 5 m or longer than 30 m. Pipe length
setting shall be performed as shown below.
(The ■ side in the DIP switch show the position.)
DSW2 on outdoor PCB1
Factory setting Factory setting Factory setting
Piping length between 5 m and ℓ(m) Pipe Length 5 m or shorter Pipe Length ℓ(m) or longer

Table of Contents

Related product manuals