10 Servicing
404
SMGB0064 rev.0 - 08/2011
7 Remove push nuts A and B which xes the compressor. Lift the compressor and remove from the unit body. (C in the
gure does not have a push nut).
a. Check if the Faston terminal has any abnormality when replacing the compressor. (Ensure the pull out force greater
than 20 N)If the Faston terminal is identied faulty replace to a new one.
b. Ensure the xture of the lead wires.
1
1
2
2
3
4
5
6
7
1. Compressor.
2. Accumulator.
3. Push nut.
4. Vibration-proof rubber.
5. Two push nuts.
6. Three vibration-proof rubber.
7. Accumulator.
Removing high pressure switch and pressure switch for control
1 Remove the pipe cover following Removing pipe cover, see on page 401.
2 Remove three (3) xing screws and remove the upper cover.
3 Remove the front cover following Removing front cover, see on page 401.
4 Collect the refrigerant from the check joint.
5 Disconnect the Faston Terminals.
6 Remove the high pressure switch and the pressure switch for control from the brazed part of discharge piping.

Table of Contents