2 Unit Installation
21
SMGB0064 rev.0 - 08/2011
2
N O T E
• All units are in mm.
• Do not stack more than two units in the height.
• If L is larger than H mount the units on a base so that H is equal or greater than L.
- H: Unit height (1650 mm) + base concret height
L A B
0 < L ≤ 1/2 H 600 or more 300 or more
1/2H < L ≤ H — —
• In this situation ensure that the base is closed and does not allow the airow to short circuit.
• In each case install the outdoor unit so that the discharge ow is not short-circuited.
• When the installation dimension results the one marked with an (*) mount the air ow guide.