8 Troubleshooting
315
SMGB0064 rev.0 - 08/2011
8
5. Touch [+] of the tester to [P] of DIP-IPM (soldered part), and [-]
to DIP-IPM U, V, W terminals to measure the resistance.
Normal if all three terminals have 1 kΩ or greater.
6. Contrary to [5], touch [-] of the tester to [P] of DIP-IPM (soldered
part), and [+] to DIP-IPM U, V, W terminals to measure the resist-
ance
. Normal if all three terminals have 30 kΩ or greater. (Resistance
gradually increases during measurement.)
7. Touch [-] of the tester to [N] of ISPM (soldered part), and [+] to
ISPM U, V, W terminals to measure the resistance.
Normal if all three terminals have 1 kΩ or greater.
8. Contrary to [7], touch [+] of the tester to [N] of DIP-IPM (sol-
dered part), and [-] to DIP-IPM U, V, W terminals to measure the
resistance.
Normal if all three terminals have 30 kΩ or greater.
(Resistance gradually increases during measurement.)
1. Tester.
2. Contact with specied terminals to measure.
Non-faulty if [9] – [13] are checked and satised.
(Measure with 1 kΩ range of a tester.)
1
2
• Internal Circuit of ACT Part of Inverter Module
1. External Appearance and Internal Circuit of Transistor Module .
N O T E
DO NOT use a digital tester
1
9. Check items [1] – [8].
10. Touch [+] of the tester to DIP-IPM DCL2 terminal, and [-] to
[P] of ISPM/DIP-IPM (soldered part) to measure the resistance.
Normal if all three terminals have 100 kΩ or greater
11. Contrary to [10], touch [-] of the tester to DIP-IPM DCL2 ter-
minal, and [+] to [P] of DIP-IPM (soldered part) to measure the
resistance.
Normal if all three terminals have 1 kΩ or greater.
12. Touch [+] of the tester to DIP-IPM DCL2 terminal, and [-] to [N]
of DIP-IPM (soldered part) to measure the resistance. Normal if
all three terminals have 100 kΩ or greater.
13. Contrary to [12], touch [-] of the tester to DIP-IPM DCL2 ter-
minal, and [+] to [N] of DIP-IPM (soldered part) to measure the
resistance.
Normal if all three terminals have 10 kΩ or greater.
(Resistance gradually increases during measurement.)
1. Tester.
2. Contact with specied terminals to measure.
1