3  Piping work and 
refrigerant charge
101
3
SMGB0077 rev.0 - 01/2013
3.4.8  Refrigerant pipe insulation
The refrigerant circulates  through  the  pipes at a very low  temperature  (several  degrees  below zero, depending on the 
time of year and the installation). The difference in temperature with the ambient air is extremely large and causes two 
signicant phenomena to be taken into account:
•  Cold irradiation along the entire pipe.
•  Condensation of the humidity in the surrounding air.
Actually, cold irradiation is the temperature gain experienced by the gas, as when it circulates under pressure and at such 
low temperatures along the inside of the pipes, it is actually liquid and obtains the outdoor temperature (boiling at a very 
low temperature) to turn into gas.
As a result of the temperature gain (although it is actually perceived as cold emission), the loses its capacity to cool and 
the system does not perform as expected. Furthermore, the humidity in the surrounding air condenses on the pipe and the 
greater the temperature difference and the longer the pipe, the more water is produced.
In view of this, the refrigerant pipes must be tted with a suitable insulation system that prevents the increase in temperature 
of the refrigerant and the subsequent loss of energy and the condensation of water along the entire pipe.
Refrigerant pipes must always be separately insulated, using closed cell insulation foam designed especially for refrigeration. 
This insulation foam, supplied by the installer, can be obtained in different formats. The most common is in the form of 
sheets and rolls of tubes of different diameters.
Furthermore, all connections between the different sections of insulation tubes must be reinforced with adhesive tape of 
the same characteristics.
Once all of the unit installation and adjustment work is complete, all threaded joints and valves must also be covered with 
adhesive tape.
3.4.9  Refrigerant pipe suspension
Only suspend the refrigerant pipes at specic points of the building. 
Whenever possible, avoid suspending them from parts subject to 
structural movement, e.g. places close to expansion joints or outer 
walls, etc.
Prevent  the  refrigerant  pipes  from  touching  weak  parts  of  the 
building,  such  as  walls  (non-structural),  partition  walls,  ceilings, 
etc. Otherwise, operating noise may be caused by pipe vibrations 
(pay special attention in the case of short pipes).
A:  points  where  the  refrigerant  pipes  pass  through  the  different 
structural parts of the building.
B: indoor unit.
A
B
1-15 mm
 
Use suitable suspension systems for refrigeration pipes or clamps 
to suspend the pipes, as shown in the diagram.