EasyManua.ls Logo

Hitachi RPI-5.0FSN4E - Page 257

Hitachi RPI-5.0FSN4E
429 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Test run
245
7
SMGB0077 rev.0 - 01/2013
13 The operating temperature:
Cooling operation
a. Indoor DB2 1.5 °C and higher.
b. Indoor WB 16 °C and higher.
c. Outdoor DB 0 °C and higher.
Heating operation
a. Indoor DB27 °C and below.
14 Use shielded cables for the installation to avoid electrical noise. This must be less than 1000 m in length and meet with
national and local regulations.
15 Disconnect the KPI unit if it is connected to the indoor unit control. Otherwise the unit will not carry out the test run.

Table of Contents

Other manuals for Hitachi RPI-5.0FSN4E

Related product manuals