8  Troubleshooting
261
8
SMGB0077 rev.0 - 01/2013
Code 
number
Category Abnormality Cause
41
Pressure
Cooling overload (possible activation of high 
pressure device)
O.U.  pipe  thermistor  temp.  is  higher  than  55  ºC  and  the 
compressor top temp. is higher than 95 ºC, O.U. protection 
device is activated.
42
Heating overload (high-pressure device may 
be activated)
If  I.U.  freeze  protection  thermistor  temp.  is  higher  than 
55 ºC and compressor top temp. is higher than 95 ºC, O.U. 
protection device is activated.
43
Activation  of  the  safety  device  from  com-
pression ratio decrease
Abnormal compress (Compressor, Inverter damage)
44
Activation of the safety device from excessi-
vely high suction pressure
Overload during cooling, high temperature with heating, 
loked expansion valve
45
Activation of the safety device from excessi-
vely high discharge pressure
Overload (obstruction of HEX, short circuit) mixture of inert 
gas
47
Activation of the safety device from exces-
sively low suction pressure (protection from 
vacuum operation)
Shortage or leakage of refrigerant, piping clogging, expan-
sion valve close-locked, fan motor locked.
48
Inverter
Abnormality of current sensor for inverter
Failure of DIP-IPM, heat exchanger clogged, locked com-
pressor, EVI/EVO failure or overcharge.
51 Abnormality of Current Sensor for Inverter  Failure of control PCB, inverter module.
53 Protection activation of inverter module
Inverter module abnormality.
Failure of compressor, clogging of heat exchanger.
54 Inverter n temperature increase
Abnormal inverter n thermistor, clogging of heat exchan-
ger, abnormal outdoor fan.
55 Inverter Module abnormality Failure of inverter module.
57 Outdoor fan Fan Motor abnormality
Disconnected wire of incorrect wiring between control PCB 
and inverter PCB.
Incorrect wiring or fan motor abnormality.
b1
Indoor unit 
number setting
Incorrect setting of the unit and the refrige-
rant cycle number.
Over 64 indoor units setting by number or indoor unit 
address.
b5
Incorrect indoor unit connection number 
setting
There are more than 17 units not corresponding to H-Link 
II connected to one system
EE Compressor Compressor protection Failure of compressor.