16
PMEN0654 rev.0 - 12/2023
5
FLARED PIPES
REFRIGERANT PIPING AND REFRIGERANT CHARGE
Before ghtening the are nut, apply the refrigerant oil (eld-supplied) of the same type and brand
that the compressor installed in the outdoor unit is using in thin layer over the aring part. Do not
apply the oil on other porons. Tighten the are nut for the liquid pipe to the specied torque with
two spanners. Then, ghten the are nut for the gas pipe in the same way. Aer ghtening work,
check that there is no refrigerant leakage.
Do not apply the refrigerant
oil to the outside of the
aring part.
Apply refrigerant oil
! CAUTION
For units with air panel be careful that the refrigerant oil does not contact the air panel because it
may cause a crack.
5.3.2 Dimensions of ared pipe
Perform the widening operaons in accordance with the measurements shown below.
Diameters (mm)
A
+0
-0.4
(mm)
Ø6.35 9.1
Ø9.52 13.2
Ø12.7 16.6
Ø15.88 19.7
Ø19.05 –
(1)
0.4-0.8R
45º ± 2º
øA
ø
d
90º±2
(1)
Not possible to perform the widening using pipe. In this case, use a connection with are tting.
5.3.3 Flared connecon mounng
Apply a thin layer of oil to the cone opening
for refrigeraon systems. Line up the end of
the ared pipe to face the ng to which it is
to be threaded.
Gently rest the female cone on the male cone
and check that the measurement is correct.
Keep the connecon lined up with one hand
and gently thread on the are nut with the
other.
Tighten the connecon to the corresponding
ghtening torque indicated in the table.
Nominal diameter
Tightening
torque
Ø6.35 1/4 20 N·m
Ø12.7 1/2 60 N·m
Ø19.05 3/4 100 N·m
Ø25.4 1 –