21
PMEN0654 rev.0 - 12/2023
5
REFRIGERANTPIPEINSULATION
REFRIGERANT PIPING AND REFRIGERANT CHARGE
CAUTION
• Do not braze on refrigerant pipes without a dry nitrogen gas injecon system. Otherwise, a layer
of rust will form that may become detached when the refrigeraon system is started, causing
lter or compressor blockages.
• NEVER USE oxygen, acetylene or uorocarbonated gas to replace nitrogen gas: this will cause an
explosion or will generate toxic gas.
Keep the nitrogen gas pressure within the indicated values. A rise in the pipe could cause an
explosion.
5.5 Refrigerant pipe insulaon
The refrigerant pipes must be ed with a suitable insulaon system that prevents the increase in
temperature of the refrigerant and the subsequent loss of energy and the condensaon of water
along the enre pipe.
Refrigerant pipes must always be separately insulated, using closed cell insulaon foam designed
especially for refrigeraon. This insulaon foam, supplied by the installer, can be obtained in
dierent formats. The most common is in the form of sheets and rolls of tubes of dierent
diameters.
Furthermore, all connecons between the dierent secons of insulaon tubes must be reinforced
with adhesive tape of the same characteriscs.
Fasten securely cord clamps and
the vinyl tape in order to prevent
the pipe from dew condensaon
Fix the vinyl tape posion at the vercal part
(Insulaon for refrigerant pipe (eld-supplied))
Refrigerant pipe
(eld-supplied)
Fasten 3 places of the
pipe by cord clamps
(eld-supplied)
Insulaon for refrigerant pipe
(eld-supplied)
Insulaon material
(factory-supplied)
Check no clearance between the indoor
unit and the insulaon
Unit side
! CAUTION
• On compleng the installaon of the refrigerant pipes, insulate the unions and are-nuts at
the piping connecon part completely, insulate them appropriately using suitable insulang
material and seal the open space between the holes made and the pipe.
• For units with air panel: If coang the oponal air panel with a forming agent (recommended
Gupoex) aer installaon, make sure that the forming agent does not contact it. Otherwise, it
could cause a breakage of the panel, resulng in the panel falling. If the forming agent contacts
the air panel, completely wipe it o.