EasyManuals Logo

Hitachi UTOPIA R32 Series User Manual

Hitachi UTOPIA R32 Series
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
48
PMEN0654 rev.0 - 12/2023
11
GENERAL CONSIDERATIONS
REFRIGERANT PUMP DOWN
11.1 General consideraons
When the refrigerant should be collected into the outdoor unit due to indoor/outdoor unit
relocaon, collect the refrigerant as follows:
Aach the manifold gauge to the gas stop valve and the liquid stop valve.
Turn ON the power source.
On outdoor unit PCB set the DSW301- pin1 ON for cooling operaon.
Close the Liquid stop valve on the unit and collect the refrigerant.
When the pressure at lower pressure side (gas stop valve) indicates -0.01 MPa (-100 mmHg),
perform the following procedures immediately.
Close the “gas stop valve” or the “High/ Low gas stop valve” depending on the unit series.
Set the DSW turned ON before at the OFF side (To stop the unit operaon).
Turn OFF the power source.
! CAUTION
Measure the low pressure by the pressure gauge and keep it not to decrease than -0.01 MPa.
If the pressure is lower than -0.01 MPa, the compressor may be faulty.
11.2 RAS-(2-3)HVRC3 refrigerant pump down example
DIP switch (DSW301 pin-1 ON)
Liquid
stop
valve
Manifold gauge
Gas stop valve

Table of Contents

Other manuals for Hitachi UTOPIA R32 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi UTOPIA R32 Series and is the answer not in the manual?

Hitachi UTOPIA R32 Series Specifications

General IconGeneral
BrandHitachi
ModelUTOPIA R32 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals