48
PMEN0654 rev.0 - 12/2023
11
GENERAL CONSIDERATIONS
REFRIGERANT PUMP DOWN
11.1 General consideraons
When the refrigerant should be collected into the outdoor unit due to indoor/outdoor unit
relocaon, collect the refrigerant as follows:
Aach the manifold gauge to the gas stop valve and the liquid stop valve.
Turn ON the power source.
On outdoor unit PCB set the DSW301- pin1 ON for cooling operaon.
Close the Liquid stop valve on the unit and collect the refrigerant.
When the pressure at lower pressure side (gas stop valve) indicates -0.01 MPa (-100 mmHg),
perform the following procedures immediately.
Close the “gas stop valve” or the “High/ Low gas stop valve” depending on the unit series.
Set the DSW turned ON before at the OFF side (To stop the unit operaon).
Turn OFF the power source.
! CAUTION
Measure the low pressure by the pressure gauge and keep it not to decrease than -0.01 MPa.
If the pressure is lower than -0.01 MPa, the compressor may be faulty.
11.2 RAS-(2-3)HVRC3 refrigerant pump down example
DIP switch (DSW301 pin-1 ON)
Liquid
stop
valve
Manifold gauge
Gas stop valve