50
PMEN0654 rev.0 - 12/2023
12
GENERALCONSIDERATIONS
H-LINK II SYSTEM
12.1 General consideraons
The H-LINK II system can not be applied to the cycle with the old H-LINK model.
1 Applicaon
The H-LINK II connecng each indoor unit and outdoor unit for up to 64 refrigerant cycles, and
connecng wires for all indoor units and all outdoor units in series.
2 Specicaons
Transmission Wire: 2-Wire.
Polarity of transmission wire: Non-Polar wire.
Maximum number of outdoor units to be connected: 64 units per H-LINK II system.
Recommended number of indoor units to be connected: 64 Units per H-LINK II system.
Maximum wiring length: total 1000 m (including CS-NET). In case that the total wiring length
is longer than 1000 m, contact the Hitachi dealer.
Recommended cable: twist pair cable with shield, over 0.75 mm2 (Equivalent to KPEV-S).
Voltage: 5 V.
Do not make a wiring in a loop.
3 DSW seng of indoor PCB and outdoor PCB.
It is recommended to set dip switches of every indoor unit and outdoor unit.

Table of Contents

Other manuals for Hitachi UTOPIA R32 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi UTOPIA R32 Series and is the answer not in the manual?

Hitachi UTOPIA R32 Series Specifications

General IconGeneral
BrandHitachi
ModelUTOPIA R32 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals