MAIN ALARM CODES
TROUBLESHOOTING
Code Category Content of Abnormality Leading Cause
01 Indoor Unit
Acvaon of protecon device 
(oat switch)
Acvaon of oat switch (high water level in drain pan, 
abnormality of drain pipe, oat switch, or drain pan)
02 Outdoor Unit
Acvaon of protecon device 
(High pressure cut)
Acvaon of PSH (pipe clogging, excessive refrigerant, 
inert gas mixing)
03
Communicaon
Abnormal communicaon 
between indoor units and 
outdoor units
Incorrect wiring, loose terminals, disconnected 
communicaon cable, blowout of fuse, indoor unit Power 
OFF
04
Abnormal communicaon 
between inverter PCB and 
outdoor PCB
Inverter PCB - outdoor PCB communicaon failure (loose 
connector, wire breaking, blowout of fuse)
05 Supply Phase
Abnormality of power supply 
phases
Incorrect power supply, connecon to reversed phase, 
Open-phase
06 Voltage Abnormal inverter voltage Outdoor voltage decrease, insucient power capacity
07
Cycle
Decrease in discharge gas 
superheat
Excessive refrigerant charge, failure of thermistor, 
incorrect wiring, incorrect piping connecon, expansion 
valve locking at opened posion (disconnect connector)
08
Increase in discharge gas 
temperature
Insucient refrigerant charge, pipe clogging, failure of 
thermistor, incorrect wiring, incorrect piping connecon, 
expansion valve locking at closed posion (disconnect 
connector)
0A Communicaon
Abnormal communicaon 
between outdoor units
Incorrect wiring, breaking wire, loose terminals
0b
Outdoor Unit
Incorrect outdoor unit address 
seng
Duplicaon of address seng for outdoor units (sub 
units) in same refrigerant cycle number
0C
Incorrect outdoor unit main unit 
seng
Two (or more) outdoor units set as "main unit" exist in 
same refrigerant cycle number
11
Sensor on 
Indoor Unit
Abnormality of inlet air 
thermistor
Incorrect wiring, disconnecng wiring, breaking wire, 
short circuit
DOAS: Dedicated outdoor air system, all fresh air indoor 
unit
12
Abnormality of outlet air 
thermistor
13
Abnormality of freeze protecon 
thermistor
14
Abnormality of gas piping 
thermistor
15
Abnormality of outdoor air 
thermistor (EconoFresh)
16
Abnormality of remote sensor 
(DOAS), not for EU market
17
Abnormality of thermistor built-
in remote controller (DOAS), not 
for EU market