63
PMEN0654 rev.0 - 12/2023
14
MAIN ALARM CODES
TROUBLESHOOTING
Code Category Content of Abnormality Leading Cause
b0
Indoor Unit
Incorrect seng of unit model
code
Incorrect seng of indoor unit model
b1
Incorrect seng of unit and
refrigerant cycle number
64 or more number is set for address or refrigerant cycle
b2 Abnormality of EEPROM EEPROM failure, incorrect data of EEPROM
b5
Incorrect indoor unit number
seng
There are 17 or more non-corresponding to H-LINK II
units are connected to one system.
b6
Abnormal communicaon
between indoor PCB and indoor
fan controller
Communicaon failure, disconnected communicaon
cable, abnormal connecon
C1
CH-Box
(Change-Over
Box)
Incorrect CH-Box connecon
2 or more CH-Box are connected between outdoor unit
and indoor unit
C2
Incorrect indoor unit connecon
number
9 or more indoor units connected to single branch type
CH-Box
7 or more indoor units connected per a branch of
mulple branch type CH-Box
C3
Incorrect indoor unit refrigerant
number seng
Indoor units of dierent refrigerant cycle number are
connected to CH-Box
C4
Incompable outdoor unit
connecon (CH-Box)
This outdoor unit is not compable with this CH-Box.
C5 Incorrect connecon port seng
Indoor unit is connected to a port that is set to not used
for mulple branch type CH-Box
EE Compressor
Compressor protecon alarm
(It can not be reset from wired
controller)
This alarm code appears when the following alarms*
occurs three mes within 6 hours
*02, 07, 08, 39, 43 to 45, 47