49
d Function
A
B
Units
Func.
Code
Name
Description

Frequency source monitor
Displays the frequency source
0Operator
1 to 15Multi-speed freq. 1 to 15
16Jog frequency
18Modbus network
19Option
21Potentiometer
23Calculate function output
24EzSQ
25[O] input
26[OI] input
27[O] + [OI]

Run command source monitor
…Control terminal
…Operator
…Modbus network
…Option

Trip counter
Number of trip events,
Range is 0. to 65530
events

Trip monitor 1
Displays trip event information:
Error code
Output frequency at trip point
Motor current at trip point
DC bus voltage at trip point
Cumulative inverter operation time
at trip point
Cumulative power-ON time at trip
point

Trip monitor 2

Trip monitor 3

Trip monitor 4

Trip monitor 5

Trip monitor 6

Warning monitor
Displays the warning code

DC bus voltage monitor
Voltage of inverter internal DC bus,
Range is 0.0 to 999.9 V
V

BRD load ratio monitor
Usage ratio of integrated brake
chopper, range is 0.0 to 100.0%
%

Electronic thermal monitor
Accumulated value of electronic
thermal detection, range is from 0.0
to 100.0%
%

Analog input O monitor
Range is 0 to 1023

Analog input OI monitor
Range is 0 to 1023

PID deviation monitor
-9999.00 to 9999.00
% times
Constant

PID output monitor
Displays PID output,
range is -100.00.to 100.00 %
%