61
b Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units

Reduced voltage
start selection
Set range, (disabling the function), (approx.
6ms) to  (approx. 1.5s)
2

Function code
display restriction
Six option codes:
Full display
Function-specific display
User setting (and )
Data comparison display
Basic display
Monitor display only
00

Initial display
selection
Initial display selection by SET key.
 to to  displayed
 displayed
B display of LCD operator
001

Automatic user
parameter
registration
Two option codes:
Disable
Enable
00

Controlled
deceleration on
power loss
Four option codes:
Trips
Decelerates to a stop
Decelerates to a stop with DC bus voltage
controlled
Decelerates to a stop with DC bus voltage
controlled, then restart
00

DC bus voltage
trigger level of ctrl.
decel.
Setting of DC bus voltage to start controlled
decel. operation. Range is 0.0 to 1000.0
220.0/
440.0
V

Over-voltage
threshold of ctrl.
decel.
Setting the OV-LAD stop level of controlled
decel. operation. Range is 0.0 to 1000.0
360.0/
720.0
V

Deceleration time
of ctrl. decel.
Range is 0.01 to 3600.0
1.0
s

Initial freq. drop of
ctrl. decel.
Setting of initial freq. drop.
Range is 0.00 to 10.0 Hz
0.0
Hz

Maximum-limit
level of window
comparator (O)
Set range, {Min.-limit level () + hysteresis
width ()x2} to 100 %
(Minimum of 0%)
100.
%

Minimum-limit
level of window
comparator (O)
Set range, 0 to {Max.-limit level () -
hysteresis width ()x2} % (Maximum of 0%)
0.
%

Hysteresis width
of window
comparator (O)
Set range, 0 to {Max.-limit level () -
Min.-limit level ()}/2 % (Maximum of 10%)
0.
%

Maximum-limit
level of window
comparator (OI)
Set range, {Min.-limit level ( + hysteresis
width ()x2} to 100 %
(Minimum of 0%)
100.
%

Minimum-limit
level of window
comparator (OI)
Set range, 0 to {Max.-limit level () -
hysteresis width ()x2} % (Maximum of 0%)
0.
%

Hysteresis width
of window
comparator (OI)
Set range, 0 to {Max.-limit level () -
Min.-limit level ()}/2 % (Maximum of 10%)
0.
%

Operation level at
O disconnection
Set range, 0. to 100.%, or no (ignore)
no
-

Operation level at
OI disconnection
Set range, 0. to 100.%, or no (ignore)
no
-