64
b Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units

Free V/F setting,
voltage.6
Set range, 0 to 800V
0.0
V

Free V/F setting,
freq.7
Set range,  to 400(580)
*1
0.
Hz

Free V/F setting,
voltage.7
Set range, 0 to 800V
0.0
V

Brake control
enable
Two option codes:
Disable
Enable/
 Enable (same as )
00
-

Brake Wait Time
for Release
Set range: 0.00 to 5.00 sec
0.00
s

Brake Wait Time
for Acceleration
Set range: 0.00 to 5.00 sec
0.00
s

Brake Wait Time
for Stopping
Set range: 0.00 to 5.00 sec
0.00
s

Brake Wait Time
for Confirmation
Set range: 0.00 to 5.00 sec
0.00
s

Brake release
freq.
Set range: 0.00 to 400.0
1
Hz
0.00
Hz

Brake release
current
Set range: 0.00 to 150 % of inverter rated
current
Rated
current
A

Braking freq.
setting
Set range: 0.00 to 400.0 Hz
0.00
Hz

Deceleration
overvoltage
suppression
enable
Disabled
Enabled
Enabled with accel.
00

Decel. overvolt.
suppress level
DC bus voltage of suppression. Range is:
200V class330 to 395
400V class660 to 790
380
/760
V

Decel. overvolt.
suppress const.
Accel. rate when b130=02.
Set range: 0.10 to 30.00 sec.
1.00
s

Decel. overvolt.
suppress
proportional gain
Proportional gain when b130=01. Range is:
0.00 to 5.00
0.20

Decel. overvolt.
suppress integral
time
Integration time when b130=01. Range is: 0.0
to 150.0
1.0
s

GS input mode
Seven option codes:
No trip (Hardware shutoff only)
E37 trip
E98/E99 trip/ display . With external
fault detection
E99 trip/ display . Without external
fault detection
Display . With external fault detection
Display input status. Without external fault
detection
Display input status. With external fault
detection
00
-

Display
ex.operator
connected
When an external operator is connected via
RS-422 port, the built-in display is locked and
shows only one "d" parameter configured in:
 to 
001