64
Free V/F setting,
voltage.6
Set range, to 400(580)
*1
Free V/F setting,
voltage.7
Two option codes:
Disable
Enable/
Enable (same as )
Brake Wait Time
for Release
Set range: 0.00 to 5.00 sec
Brake Wait Time
for Acceleration
Set range: 0.00 to 5.00 sec
Brake Wait Time
for Stopping
Set range: 0.00 to 5.00 sec
Brake Wait Time
for Confirmation
Set range: 0.00 to 5.00 sec
Set range: 0.00 to 400.0
1
Hz
Set range: 0.00 to 150 % of inverter rated
current
Set range: 0.00 to 400.0 Hz
Deceleration
overvoltage
suppression
enable
Disabled
Enabled
Enabled with accel.
Decel. overvolt.
suppress level
DC bus voltage of suppression. Range is:
200V class330 to 395
400V class660 to 790
Decel. overvolt.
suppress const.
Accel. rate when b130=02.
Set range: 0.10 to 30.00 sec.
Decel. overvolt.
suppress
proportional gain
Proportional gain when b130=01. Range is:
0.00 to 5.00
Decel. overvolt.
suppress integral
time
Integration time when b130=01. Range is: 0.0
to 150.0
Seven option codes:
No trip (Hardware shutoff only)
E37 trip
E98/E99 trip/ display . With external
fault detection
E99 trip/ display . Without external
fault detection
Display . With external fault detection
Display input status. Without external fault
detection
Display input status. With external fault
detection
Display
ex.operator
connected
When an external operator is connected via
RS-422 port, the built-in display is locked and
shows only one "d" parameter configured in:
to