63
Cooling fan
control
(NOTE 1)
Selects when the fan is ON during inverter
operation, three options:
Fan is always ON
Fan is ON during run, OFF during stop (5
minute delay from ON to OFF)
Fan is temperature controlled
Clear elapsed
time of cooling fan
(NOTE 1)
Two option codes:
Count
Clear
Initialization target
data
Select initialized parameters, four option
codes:
All parameters
All parameters except in/output terminals
and communication.
Only registered parameters in xxx.
All parameters except registered
parameters in xxx and .
Dynamic braking
control (BRD)
selection
Three option codes:
Disable
Enable during run only
Enable always
Range is:
330 to 380V (200V class)
660 to 760V (400V class)
Set the value of the resistor connected to the
the inverter hardware is calculated
automatically.
Range is minimum connectable resistor Rbmin
to 600.0Ω
Set range, 0 to value of
Free V/F setting,
voltage.1
Set range, value of to
Free V/F setting,
voltage.2
Set range, value of to
Free V/F setting,
voltage.3
Set range, value of to
Free V/F setting,
voltage.4
Set range, value of to
Free V/F setting,
voltage.5
Set range, value of to