71 
 
Input Function Summary Table – This table shows all thirty-one intelligent input functions 
at a glance. Detailed description of these functions, related parameters and settings, and 
example wiring diagrams are in “Using Intelligent Input Terminals” on page 29. 
Input Function Summary Table 
Inverter is in Run Mode, motor runs forward 
Inverter is in Stop Mode, motor stops 
Inverter is in Run Mode, motor runs reverse 
Inverter is in Stop Mode, motor stops 
Multi-speed Select, 
Bit 0 (LSB) 
Binary encoded speed select, Bit 0, logical 1 
Binary encoded speed select, Bit 0, logical 0 
Multi-speed Select, 
Bit 1 
Binary encoded speed select, Bit 1, logical 1 
Binary encoded speed select, Bit 1, logical 0 
Multi-speed Select, 
Bit 2 
Binary encoded speed select, Bit 2, logical 1 
Binary encoded speed select, Bit 2, logical 0 
Multi-speed Select, 
Bit 3 (MSB) 
Binary encoded speed select, Bit 3, logical 1 
Binary encoded speed select, Bit 3, logical 0 
Inverter is in Run Mode, output to motor runs at jog 
parameter frequency 
DC braking will be applied during deceleration 
DC braking will not be applied 
Set  (select)  2nd  Motor 
Data 
The inverter uses 2nd motor parameters for 
generating frequency output to motor 
The inverter uses 1st (main) motor parameters for 
generating frequency output to motor 
2-stage Acceleration and 
Deceleration 
Frequency output uses 2nd-stage acceleration and 
deceleration values 
Frequency  output  uses  standard  acceleration  and 
deceleration values 
Causes  output to  turn OFF,  allowing motor  to  free 
run (coast) to stop 
Output operates normally, so controlled deceleration 
stop motor 
When assigned input transitions OFF to ON, inverter 
latches trip event and displays  
No  trip  event  for  ON  to  OFF,  any  recorded  trip 
events remain in history until reset 
Unattended Start 
Protection 
On  powerup,  the  inverter  will  not  resume  a  Run 
command (mostly used in the US) 
On  powerup,  the  inverter  will  resume  a  Run 
command that was active before power loss 
Commercial  power 
source switchover 
Motor can be driven by commercial power 
Motor is driven via the inverter 
The  keypad  and  remote  programming  devices  are 
prevented from changing parameters 
The parameters may be edited and stored 
Analog Input 
Voltage/Current Select 
Refer to “Analog Input Operation” on page 43. 
The trip condition is reset, the motor output is turned 
OFF, and powerup reset is asserted 
Normal power-ON operation 
PTC thermistor  Thermal 
Protection 
(C005 only) 
When a thermistor is connected to terminal [5] and 
[L], the inverter checks for over-temperature and will 
cause trip event and turn OFF output to motor 
A disconnect of the thermistor causes a  trip event, 
and the inverter turns OFF the motor