- 19 -
Func.
Code
Name / Description
Default value
-FE/FU
Set
value
y 04 Decelerate to a stop
C077 Communication error time-out 0.00
C078 Communication wait time 0.
C081 O input span calibration 100.0
C082 OI input span calibration 100.0
C086 AM offset calibration 100.0
C091 Debug mode enable
y 00 No Display y 01 Display
00
<Do not change>
00
C101 Up/Down memory mode selection
y 00
Clear last frequency
(return to default freq. F001)
y 01 Keep last freq. adjusted by Up/Down
00
C102 Reset selection
y
00 Cancel trip state at input signal ON transition,
stops INV if in Run Mode
y
01 Cancel trip state at input signal OFF
transition, stops INV if in Run Mode
y
02 Cancel trip state at input signal ON transition,
no effect if in Run Mode
00
C141
Input A select for logic output
00
C142
Input B select for logic output
Twelve option
codes available
see page 20
01
C143 Logic function select
y 00 [LOG] = A AND B
y 01 [LOG] = A OR B
y 02 [LOG] = A XOR B
00
C144 Terminal [11] ON delay 0.0
C145 Terminal [11] OFF delay 0.0
C148 Output relay ON delay 0.0
C149 Output relay OFF delay 0.0
“H” group: Motor Constants Functions
Func.
Code
Name / Description
Default
-FE/FU
Set
value
H003/
H203
Motor capacity Factory
set
H004/
H204
Motor poles setting
y
2
y
4
y
6
y
8
4
H006/
H206
Motor stabilization constant 100