Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are
presented in the tables below.
Motor Output Torque
Input
Voltag e
kW HP
Inverter Model
Power Terminal
Wiring Size
Range (AWG)
Ft-lbs (N-m)
0.2 1/4
X200-002SFE/NFU
0.4 1/2
X200-004SFE/NFU
0.6 0.8
0.55 3/4
X200-005SFE
0.75 1
X200-007SFE/NFU
14
(75°C only)
1.1 1 1/2
X200-011SFE
1.5 2
X200-015SFE/NFU
12
2.2 3
X200-022SFE/NFU 10
0.9 1.2
3.7 5
X200-037LFU 10
0.9 1.2
5.5 7 1/2
X200-055LFU
200V
7.5 10
X200-075LFU
8
1.5 2.0
0.4 1/2
X200-004HFE/HFU
0.75 1
X200-007HFE/HFU
1.5 2
X200-015HFE/HFU
16
(75°C only)
2.2 3
X200-022HFE/HFU
3.0 4
X200-030HFE
4.0 5
X200-040HFE/HFU
14
(75°C only)
0.9 1.2
5.5 7 1/2
X200-055HFE/HFU
400V
Class
7.5 10
X200-075HFE/HFU
10
1.5 2.0
Torque
Terminal Connector
Wiring Size
Range (AWG)
Ft-lbs (N-m)
Logic and Analog connectors 30 – 16 0.16 – 0.19 0.22 – 0.25
Relay connector 30 – 14 0.37 – 0.44 0.5 – 0.6
Wire Connectors
WARNING: Field wiring connections
must be made by a UL Listed and CSA
certified ring lug terminal connector
sized for the wire gauge being used.
The connector must be fixed using the
crimping tool specified by the
connector manufacturer.