Circuit Breaker and Fuse Sizes 
 
The inverter’s connections to input power for 400V class units must include 
UL Listed inverse time circuit breakers with 600V rating, or UL Listed fuses 
as shown in the table below. 
 
Input  
Voltag e 
Inverter Model 
Circuit breaker / 
Fuse 
Ampere rating for
Fuse or Breaker 
X200-002SFFE/NFU 
X200-004SFFE/NFU 
X200-005SFFE 
10 
X200-007SFFE/NFU 
X200-011SFFE 
15 
X200-015SFFE/NFU 20 
X200-022SFFE/NFU 
X200-037LFU 
30 
X200-055LFU 40 
Single/ 
Three- 
Phase 
200V 
X200-075LFU 
Inverse time circuit 
breaker 
50 
X200-004HFE/HFU 3 
X200-007HFE/HFU 6 
X200-015HFE/HFU 10 
X200-022HFE/HFU 10 
X200-030HFE 15 
X200-040HFE/HFU 15 
X200-055HFE/HFU 20 
Three- 
Phase 
400V 
X200-075HFE/HFU 
Distribution Fuse 
(Class J) 
25 
 
 
Motor Overload Protection 
 
Hitachi X200 inverters provide solid state motor overload protection, which 
depends on the proper setting of the following parameters: 
•  B012 “electronic overload protection” 
•  B212 “electronic overload protection, 2nd motor” 
Set the rated current [Amperes] of the motor(s) with the above parameters. The 
setting range is 0.2 * rated current to 1.0 * rated current. 
 
WARNING: When two or more motors are connected to the inverter, they 
cannot be protected by the electronic overload protection. Install an external 
thermal relay on each motor.