List of Holding Registers
Network Data
Func.
Code
Name R/W Description
Reg. Range Res.
A051 DC braking enable R/W Two options; select codes:
00...Disable
01... Enable
02... Frequency detection
1051h 0, 1, 2
A052 DC braking frequency
setting
R/W The frequency at which DC
braking begins, range is from the
start frequency (B082) to 60 Hz
1052h (B082 x 10)
to 600
0.1 Hz
A053 DC braking wait time R/W The delay from the end of
controlled deceleration to start of
DC braking (motor free runs
until DC braking begins),
range is 0.0 to 5.0 sec.
1053h 0 to 50
A054 DC braking force for
deceleration
R/W Level of DC braking force,
settable from 0 to 100%
1054h 0 to 100 1 %
A055 DC braking time for
deceleration
R/W Sets the duration for DC
braking, range is 0.0 to 60.0
seconds
1055h 0 to 600 0.1 sec
A056 DC braking / edge or
level detection for [DB]
input
R/W Two options; select codes:
00... Edge detection
01... Level detection
1056h 0, 1
A061 Frequency upper limit
setting
R/W Sets a limit on output frequency
less than the maximum
frequency (A004). Range is from
frequency lower limit (A062) to
maximum frequency (A004).
0.0.. setting is disabled
>0.1 setting is enabled
105Ah (A062 x 10)
to (A004 x
10),
0=disable
>1=enable
A261 Frequency upper limit
setting, 2nd motor
R/W Sets a limit on output frequency
less than the maximum
frequency (A204). Range is from
frequency lower limit (A262) to
maximum frequency (A204).
0.0.. setting is disabled
>0.1 setting is enabled
1517h (A262 x 10)
to (A204 x
10),
0=disable
>1=enable
0.1 Hz
A062 Frequency lower limit
setting
R/W Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
105Bh (B082 x 10)
to (A061 x
10),
0=disable
>1=enable
A262 Frequency lower limit
setting, 2nd motor
R/W Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
1518h (B082 x 10)
to (A261 x
10),
0=disable
>1=enable
0.1 Hz
A063,
A065,
A067
Jump (center)
frequency setting
R/W Up to 3 output frequencies can be
defined for the output to jump
past to avoid motor resonances
(center frequency)
Range is 0.0 to 400.0 Hz
105Dh
1060h
1063h
0 to 4000 0.1 Hz
A064,
A066,
A068
Jump (hysteresis)
frequency width
setting
R/W Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz
105Eh
1061h
1064h
0 to 100 0.1 Hz
B27
Appendix B
B
27
Appendix B

Table of Contents